Axial Fan Performance Test

Measured a fan across 11 operating points, calculated flow and efficiency, and checked a lower-speed prediction against one physical test.

Role
Testing, calculations, and individual report
Year
2026

Question

How do pressure rise and efficiency change with flow, and can fan laws predict another speed?

My work

Reduced Pitot-static and power readings, calculated 80% performance, and scaled the results to 30% speed.

Finding

Gross efficiency reached 36% in the measured set. The single 30% pressure check fell below nearby predictions.

Performance data

Pressure rise versus flow rate

The left plot shows the 11 measured 80% operating points. The right plot shows fan-law predictions at 30% and the one measured check. Each panel uses its own scale so the low-speed result remains readable.

80% speed · measured

11 damper settings

Measured 80 percent fan-speed pressure rise

30% speed · prediction and check

Hollow circles: predicted · gold diamond: measured

Predicted and measured 30 percent fan-speed pressure rise

Plotted from the measured and scaled values in my ME 347 individual report. The markers show data points; no fitted curve is implied.

What I did

From instrument readings to fan performance

01

Set operating points

Changed duct damper settings across the 80% speed test range.

02

Measure response

Used Pitot-static readings in both ducts, fan pressure rise, and input-power data.

03

Calculate performance

Calculated flow rate, power added to the air, and gross efficiency at each point.

04

Check the scaling law

Predicted 30% pressure and flow, then compared them with one test point at that speed.

Results

What the data showed

  • 798–3298 cfm across the measured 80% flow range.
  • 0.42–1.25 in H₂O pressure rise across that range.
  • 36% gross efficiency at the highest reported efficiency point, 2966 cfm.

Limit of the comparison

A lower measured pressure

At 30% speed, the measured point was 1071 cfm and 0.050 in H₂O. The nearest tabulated prediction was 1112 cfm and 0.084 in H₂O. The flows differ slightly, but the pressure gap is substantial. One check point without quantified measurement uncertainty cannot validate the full lower-speed curve.

A repeat test across several 30% operating points would help determine whether this gap persists.